Contact Rating |
10A @ 600V AC |
For Use With |
Chrome, Plastic Operators (ZB4 or ZB5 Operators) |
Action |
Momentary |
Color |
Black/Green |
Application |
Operator |
Contact Form |
1NO |
Terminal Connection |
Screw/Clamp |
Standards |
CSA, UL |
NEMA Contact Rating Designation |
A600/Q600 |
Device Short Name |
ZBE |
Shape Of Screw Head |
cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm |
[Ie] Rated Operational Current |
3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 || 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1 |
Ambient Air Temperature For Operation |
-40-70°C |
Protective Treatment |
TH |
Shock Resistance |
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
Vibration Resistance |
5 gn 2-500 Hz)IEC 60068-2-6 |
[Ith] Conventional Free Air Thermal Current |
10 A EN/IEC 60947-5-1 |
Short-Circuit Protection |
10 A cartridge fuse gG EN/IEC 60947-5-1 |
Operating Force |
2.3 N NO changing electrical state |
Mounting Of Block |
front mounting |
[Ui] Rated Insulation Voltage |
600 V 3)EN 60947-1 |
Contact Operation |
slow-break |
Ambient Air Temperature For Storage |
-40-70°C |
Tightening Torque |
0.8-1.2 N.m EN 60947-1 |
Contacts Material |
silver alloy (Ag/Ni) |
Electrical Composition Code |
C1 9 ) || C2 7 ) || C3 6 ) || C4 4 ) || C5 5 ) || C6 3 ) || C7 4 ) || C8 2 ) || C9 3 ) || C12 6 ) || M1 6 ) || M2 4 ) || M3 4 ) || M5 2 ) || M6 2 ) || M7 6 ) || M8 4 ) || M9 2 ) || SF1 3 ) || SF2 2 ) || MF1 2 ) || MF2 2 ) || C10 2 ) || M4 2 ) || C13 1 ) |
Product Or Component Type |
contact block |
Operating Travel |
2.6 mm NO changing electrical state) || 4.3 mm total travel) |
Electrical Durability |
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C |
[Uimp] Rated Impulse Withstand Voltage |
6 kV EN 60947-1 |
Contact Block Type |
single |
Contacts Usage |
standard contacts |
Contacts Type And Composition |
1 NO |
Ip Degree Of Protection |
IP20 IEC 60529 |
Positive Opening |
without |
Device Presentation |
basic element |
Product Certifications |
CCC || UL || DNV || GL || GOST || LROS (Lloyds register of shipping) || BV || CSA |
Mechanical Durability |
10000000 cycles |
Connections - Terminals |
screw clamp terminals, <= 2 x 1.5 mm² with cable end EN 60947-1 || screw clamp terminals, >= 1 x 0.22 mm² without cable end EN 60947-1 |